CHARACTERISTICSFire resistance

Fire resistance tests were carried out as per EN 1363-1 and EN 1365-1 (tests carried out at the UG unit, University of Ghent)

Supporting wall Vartical joints Coating(*) Heat insulation Proofing Wall stability Flame passage
9 cm Blocks
No Open Plaster 152 min >182 min >182 min No
No Closed None 111 min >127 min >127 min No
No Open None 105 min >135 min >135 min No
14 cm Blocks
Yes Open Plaster 346 min >360 min >360 min No
Yes Open None 281 min >360 min >360 min No
19 cm Blocks
No Open None >360 min >360 min >360 min No
Yes Open None 333 min >360 min >360 min No

(*) «Plaster» means that a layer of plaster ± 3-5 mm thick is applied on either side of the wall.
Besto® blocks correspond to EURO Class A1 (fire reaction – European Commission decision n° 96/603/EC).    
  

 
Test on coated wall

Test on uncoated wall




   
 